This is the module where underfloor stops being a nice idea and becomes a number. Everything up to here — the construction, the covering, the manifold — exists to deliver a particular watts-per-square-metre figure to a particular room. This article is how you find that figure, and how you find out honestly whether the floor can produce it.
It covers Module 5 of the PlumbMate underfloor heating course: the heat loss inputs, watts per square metre, the surface temperature limits and the emission formula behind them, pipe layouts and centres, pipe quantity, flow rates, and the performance chart check that decides whether the design works. There is a 10-question mock test at the end.
The heat loss, and what goes into it
The method is BS EN 12831, worked room by room; for houses, the CIBSE Domestic Heating Design Guide sets out the same method. The inputs are the room dimensions, the building fabric, the room temperatures (21 °C for living rooms, 18 °C for kitchens, halls and bedrooms, 22 °C for bathrooms), the outside design temperature, the air change rates and the floor losses. Boiler efficiency is not an input — the heat loss belongs to the building.
For a new dwelling, the U-values worth carrying are the limiting values in Approved Document L (2021, Volume 1), Table 4.1:
- Floors — 0.18 W/m²K
- Walls — 0.26 W/m²K
- Roofs, all types — 0.16 W/m²K
- Windows and doors — 1.6 W/m²K
These are the worst each element may be, and a new home usually needs some elements well inside them to meet its target fabric energy efficiency rate. Work on an existing dwelling uses Tables 4.2 and 4.3 instead. A new floor in an extension is limited to 0.18 W/m²K (Table 4.2), and an existing floor that is being renovated is brought to 0.25 W/m²K (Table 4.3).
Then comes the step that is specific to underfloor. A radiator design stops at a number of watts. An underfloor design divides that by the heated floor area to get watts per square metre, because that is the unit the floor is judged in.
The house worked through below is a new single-storey house with eight heated rooms, built to the notional dwelling values (walls 0.18, floor 0.13, roof 0.11, windows 1.2 W/m²K) and heated by an air source heat pump. Its lounge, 22 m² at 21 °C with −3 °C outside, loses 1,113 W: 486 W through its walls, glazing, floor, ceiling and the walls to the cooler hall and kitchen, and 627 W in air change. A wall to the unheated porch counts as an outside wall. Over its 22 m² of floor that is 50.6 W/m². Divide by the active area, the floor you can lay pipe in: no pipe goes under kitchen units or a shower tray.
Surface temperature limits, and where they come from
Three design conditions, each pairing a surface temperature with a room temperature and an output:
- Occupied area — 29 °C surface, 20 °C room, 100 W/m²
- Bathroom — 33 °C surface, 24 °C room, 100 W/m²
- Peripheral area — 35 °C surface, 20 °C room, 175 W/m²
Covering limits can pull those down — vinyl and laminate cap at 27 °C regardless.
Those are not three facts to memorise separately. They come out of one formula:
q = 8.92 × (AFST − ART)1.1, in W/m²
where AFST is the average floor surface temperature and ART is the average room temperature. Put 29 over 20 into it and you get exactly 100 W/m². Put 35 over 20 in and you get 175. The table is the formula, worked at the limits.
The 1.1 exponent is there mainly because natural convection strengthens as the floor warms, so output rises a little faster than the temperature difference. It is also why the formula is worth knowing rather than just the table: read it backwards and you can answer the more useful question. A room that needs 60 W/m² wants a floor at around 25.7 °C — comfortably inside the cap, with room to spare.
Three things set the surface temperature you actually get: the floor covering, the pipe spacing, and the water temperature.
Layout and centres
Two layouts, and the difference between them is real:
- Series, or meander. The pipe switches back on itself across the room. The water cools progressively along the run, so a meander is started at the coldest side of the room — usually the external wall.
- Spiral, also called snail or bifilar. Flow and return run alongside each other the whole way, so a cooling flow pipe always has a warm return pipe next to it. The result is a far more even floor temperature.
Both come in standard and modified forms; modified concentrates pipe where the loss is greatest.
What actually influences the choice of layout: the surface finish limits, the surface area and the circuit length limit, the distance from the room to the manifold, and unequal perimeter energy. What does not influence it: the boiler type, the radiator sizes, or the water temperature.
Pipe sizes are 15, 16, 18 and 20 mm. Centres are 100, 150, 200, 250 and 300 mm. 200 mm is the generally accepted spacing on a screeded floor over floor-grade insulation.
Two refinements. Run the flow round the outside wall first, at 150 mm — closer centres put more output where the wall is losing most. And where several circuits bunch together crossing a hallway on their way elsewhere, insulate the individual pipes through that stretch, or the hall floor will overheat with heat that no room thermostat has any authority over.
Pipe quantity and coil length
The arithmetic is one line:
Pipe length = floor area ÷ spacing in metres
20 m² at 200 mm centres is 20 ÷ 0.2 = 100 m. The mistake to watch for is multiplying instead of dividing: 20 × 0.2 gives 4 m, which should stop anybody in their tracks.
Then add the flow and return tails back to the manifold, measured for each room: the farther the room, the longer they are. Bedroom 1 of the worked house has 10.8 m² of active floor at 200 mm centres, 4 m from the manifold:
- 10.8 ÷ 0.2 = 54 m of pipe in the floor
- plus 4 + 4 m of tails = 62 m
Then the rule that matters: each circuit has a maximum length, about 100 m in 16 mm pipe on most makers' tables, tails included. The lounge, 22 m² at 200 mm with 3 m tails, would be 110 + 6 = 116 m as one circuit, so it becomes two circuits of about 61 m.
The coils come last. Makers sell 16 mm pipe in coils from about 50 m to 500 m. The house's nine circuits come to 509.5 m, just over one 500 m coil, so it takes a 500 m coil and a 100 m coil, with every circuit cut whole, because pipe within the floor is laid without joints. There is no making up a shortfall. On a larger scheme the economical method is the manufacturer's tube trimming charts, which fit the circuits to the coils across the whole job rather than room by room.
Flow rates
One formula:
kW ÷ 4.2 ÷ ΔT × 60 = litres per minute, where ΔT is the drop in temperature from flow to return.
4.2 is the specific heat capacity of water in kJ/kg·K, and the density is 1 kg per litre, which is what lets kilograms and litres be used interchangeably here.
Two rooms from the worked house, both at a flow–return drop of 5 K:
- Bedroom 1 — 376 W = 0.376 kW → 0.376 ÷ 4.2 ÷ 5 × 60 = 1.07 l/min
- Garden room — 1,583 W = 1.583 kW → 1.583 ÷ 4.2 ÷ 5 × 60 = 4.52 l/min, nearly three times the kitchen's 1.65 from a floor the same size
A word about that drop. BS EN 1264-3 sets a flow-to-return drop of 5 K or less for the design room, the room that needs the most output; other rooms may run wider. The worked house runs every circuit at 5 K, which keeps it simple and inside the standard. Whatever the design runs at is the figure the arithmetic uses, and a narrower drop always means a higher flow for the same output.
Will it actually work?
The last step is the one that separates a design from a hope. Manufacturers' performance charts take four inputs — water temperature, room temperature, pipe centres and floor covering resistance — and give two outputs: the heat emission in W/m², and the resulting floor surface temperature.
Read those off, room by room, and compare with what each room needs. Read each room at its own temperature: the chart's output depends on how far the mean water sits above the room, so a warmer room takes less from the same water. On the worked house, at a 40 °C flow and 35 °C return (the course's own chart, worked out from BS EN 1264-2):
- Hall, kitchen and both bedrooms — pass comfortably (the kitchen 72.0 against 56.7 W/m²)
- Study — passes, but its laminate is at 26.7 °C against its 27 °C limit
- Lounge, 1.5 tog carpet — 42.8 W/m² against 50.6
- Shower room at 22 °C — 85.9 W/m² against 101.4; its small active floor leaves the towel rail to make up the rest
- Garden room, glazed on three sides and roofed in glass — 91.4 W/m² against 123.7, with the floor already past 29 °C
The lounge falls short on its covering: a 1 tog carpet gives 50.2, still just short, but with the centres closed to 150 mm as well it gives 55.6 and passes. The garden room needs more than any floor can give, since the 29 °C cap allows about 88 W/m² in a 21 °C room.
That is not a failure of the method. It is the method working: it has told you, before anything is buried, exactly which rooms need attention. Four levers, in the order you should reach for them:
- Close the pipe centres — cheap now, impossible later
- Change the covering — if the choice is still open
- Raise the flow temperature, within the 55 °C limit and whatever the floor finish allows
- Add supplementary heat — the honest answer for the glass-roofed garden room
📝 10-Question Mock Test
Click an option to see whether you got it right. Explanations appear instantly — no submitting at the end.
Approved Document L, Table 4.1, limits a new dwelling to 0.18 for floors and 0.26 for walls, with roofs at 0.16 and windows and doors at 1.6 W/m²K. 0.13 and 0.18 are the notional dwelling's floor and walls (Table 1.1), used to set the target, not the limits. 0.25 and 0.35 are old figures.
35 °C over a 20 °C room gives 175 W/m². Occupied areas are 29 over 20 for 100, and a bathroom 33 over 24 for 100.
AFST is the average floor surface temperature and ART the average room temperature. Put 29 over 20 in and it gives exactly 100 W/m²; 35 over 20 gives 175.
The exponent comes mainly from natural convection: the warmer the floor, the faster the air moves over it, so each extra degree gives a little more than the last. Read it backwards and it becomes useful rather than academic: 60 W/m² needs a floor at only about 25.7 °C, comfortably inside the cap.
In a spiral, a cooling flow pipe always has a warmer return pipe beside it. A meander cools progressively along the run, which is why it is started at the coldest side of the room.
The wall that loses most gets the hottest water. Take the flow from the manifold along it first, with the runs closed up to about 150 mm, then fill the rest of the room at the general spacing. Starting at the door, or running the cooled return along the wall, gives the coldest edge the coolest water.
110 + 6 = 116 m is over the circuit limit, so the lounge gets two circuits of 55 + 6 = 61 m. The tails are part of the circuit, and there is no jointing round it, because pipe within the floor is laid without joints.
20 m² at 200 mm centres is 20 ÷ 0.2 = 100 m. Multiplying instead would give 4 m, which should stop anybody in their tracks.
376 W = 0.376 kW. Then 0.376 ÷ 4.2 ÷ 5 × 60 = 1.07 l/min. The 4.2 is the specific heat capacity of water in kJ/kg·K; stop before the × 60 and you have kilograms per second.
Closer centres are cheap now and impossible once the pipe is buried. Then the covering, then the flow temperature within limits, and supplementary heat last.
The reason to work all eight rooms rather than the worst one is that you cannot tell in advance which rooms will fail. A glass-roofed garden room, a lounge with a thick carpet and a shower room with little floor left fall short for completely different reasons, and all three would have looked fine on a whole-house average. Room by room, before the screed, is the only version of this that is worth anything.