A method beats a hunch. That is the whole of this module, and the reason is that solar faults divide into three groups that look identical from the doorstep: things that are broken, things that are set wrong, and things that are working exactly as designed.

This article covers Module 7 of the PlumbMate solar thermal course: routine servicing to BS 5918, stagnation and fluid degradation, working a fault from the symptom, the faults with one distinctive sign, and what to do after rectification. There is a 10-question mock test at the end.

Routine servicing

A solar primary lives a harder life than a heating circuit: it is outdoors, it swings between ambient and stagnation, and its fluid degrades with heat. Maintenance is what keeps that from turning into failure.

A house cut open from the side with the solar system marked with its annual checks, and the airing cupboard drawn larger. Outside the building: 1 the collector glazing clean and uncracked; 2 the fixings firm and the roof covering under the collectors sound; 3 a tree grown into the array's sunlight; 4 the outdoor pipe insulation, shown pecked, split and faded by UV. Inside the building: 5 loft insulation gaps at brackets and valves; 6 damp staining round a pipe and a fixing in the roof space, where a slow leak shows first; 7 the gauge against its red pointer at the recorded cold fill figure; 8 the relief valve tested and its discharge into its container; 9 the expansion vessel on the return; 10 the strainer, cleaned; 11 the air vent, and whether air keeps recurring; 12 the controller and its settings as recorded; 13 the store sensor in its pocket level with the solar coil; 14 the collector sensor lead secure.
The annual service, round the system: outside the building, then inside.

The BS 5918 shape of an inspection

The standard splits the visit in two, which is a useful way to work through it.

Outside the building: the collector glazing is clean; the glazing is sound and free of cracks; there is no evidence of serious corrosion; any paintwork is sound; roof fixings are firm and the covering beneath the collectors is free from cracks and abrasions.

Inside the building: the sensing devices are firmly and properly in place; there are no signs of corrosion; labels are in position and updated at the time of the visit; and the life of the heat transfer fluid has not expired.

Add to those the post-commissioning items: unions and glands free of weeps, glazing seals weathertight, all air expelled, sealed systems at the correct pressure, controls and indicators operating, the pump running without undue noise, insulation firmly attached, and no condensation or damp spots — particularly around pipes and fixings in the roof space, which is where a slow leak shows up first.

The annual checks

Longer intervals

The two records a visit produces

They are two documents because they answer two questions. The maintenance record says the system was checked; the fault record says what was wrong and what was done about it — including what you eliminated on the way, which is what tells the next engineer where not to start.

Stagnation and fluid degradation

One fully filled solar system on a summer's day, in four frames. 1, morning: the pump runs, the store charges at 40 °C and the collector flow reads 65 °C. 2, early afternoon: the store reaches its maximum of 65 °C, as commissioned within 60 to 65 °C, and the controller stops the pump; the other causes, a power cut, a pump or controller failure and a holiday, are shown small. 3, the sun still on it with no flow: the collector reaches its stagnation temperature, flat plate over 200 °C, evacuated tube around 350 °C, and the fluid in it turns to vapour and pushes down into the expansion vessel. 4, after many summers: a sample jar going from clear to brown; the inhibitors are used up and the fluid turns acidic, pH below 7: replace it, never top up. Footnote: the first defence is design, a 50 to 60% solar fraction or drain-back.
The fluid is a consumable: once stagnation has used up its inhibitors, replace it, never top it up.

Stagnation occurs when the collector is receiving solar energy but the pump is not running and no heat is being removed — a power cut, a controller or pump failure, a fully charged store on a hot day, or a holiday with no draw-off. The collector simply keeps absorbing until it reaches its stagnation temperature: the point at which losses equal the energy coming in.

That is why flat plate collectors reach over 200 °C and evacuated tubes around 350 °C (the CIBSE figures), and why the fluid, seals, insulation and jointing must all be rated for it.

What it does to the fluid

Repeated stagnation degrades the glycol and exhausts its inhibitor package. Once the inhibitors are spent, the fluid turns acidic and begins corroding the system from within. The visible signs are darkened or brown fluid, a sharp or burnt smell, and a pH below 7. Any of those means replacement — topping up simply dilutes exhausted fluid with fresh.

Managing it by design

Correct sizing is the first defence: an oversized array spends the summer stagnating for no extra benefit, which is why a 50–60% solar fraction is the target rather than the largest array that will fit. A drain-back design protects the fluid, since the collector empties whenever the pump stops; the empty collector still stagnates, with nothing in it to cook.

Changing the fluid

Cover the collectors, isolate and allow the system to cool — never drain a hot collector — drain and flush thoroughly, refill with correctly pre-mixed fluid, purge, reset the pressure and verify the freezing point with a refractometer. Dispose of the old fluid through the proper waste route, following the safety data sheet. Glycol is a hazardous substance and does not go down a drain.

Fault finding: no heat and poor performance

Fault finding is a discipline, not a guess: establish the symptom, list the plausible causes, and check them in ascending order of cost and disruption. The cheapest checks often find the fault, and they cost little to rule out.

Pump not running

Check in this order: electrical supply — is the spur switched on and the fuse intact; controller settings — is the differential still as recorded; sensors — are they reading plausibly; then the pump itself.

Two more causes belong on that list before you condemn the pump. The cylinder may have reached its maximum temperature — at 65 °C the controller stops charging, and the system is behaving exactly as commissioned. And the rotor may be seized by deposits rather than the motor being dead: many circulators can be freed by switching briefly to maximum speed, or, where the maker allows, by taking out the vent screw on the end of the motor and turning the shaft with a screwdriver.

Short-cycling, or "clocking"

The pump starts, runs briefly, stops, and repeats — typically in the morning and again in the evening. The causes are a switch-on differential set too small, a pump speed set too high, or a collector sensor in the wrong place or left uninsulated, which reads a spike the rest of the circuit cannot sustain. The remedies follow directly: widen the differential, drop the pump speed, and get the sensor into the flow and insulated.

The mirror image is a pump that starts late and stops early, which points to a switch-on differential set too high, or uninsulated collector connection pieces on a tube collector.

Pump runs but no heat reaches the store

Suspect airlock first, then a closed or partly closed isolation valve, then a blocked or fouled heat exchanger, then a non-return valve fitted the wrong way round, which blocks the flow. Reading temperatures either side of the exchanger separates a circulation problem from a transfer problem quickly.

If the pump is running hot with flow and return at the same temperature, that is air. Check the system pressure, run the pump intermittently at maximum, and vent at the pump, the cylinder and the non-return valve. If it keeps coming back, the pipework itself is the problem — a dip over a beam or around a bend holds air the vents cannot reach, and the answer is to re-route or add a vent at that high point.

Poor performance with everything apparently working

Check the flow rate against the commissioned figure, the glycol concentration — over-concentrated fluid carries less heat — insulation condition, and new shading, which is easily missed on a system that was fine for three summers and then had a tree grow into it.

The store sensor

A sensor fitted too high reads water the boiler has already heated. The controller sees no useful differential and the pump seldom runs. Nothing is faulty and every component tests good — which is precisely why it is missed. If a system has never performed since installation, check the sensor position before anything else.

Overheating, pressure loss and air

Pressure loss with nothing discharging

When the gauge falls but there is no wet patch and no sign of the relief valve passing, work through three explanations before assuming a hidden leak:

If it keeps falling after all three are excluded, then it is a leak — and the places to look are the screwed connections and glands at valves, then the soldered joints, then the collector array itself, where a tube or a collector may need replacing.

Sluggish circulation with a healthy pump

Sluggish circulation with a healthy pump points to viscosity that is too high: glycol mixed too strong, or a cold circuit on a winter morning. It is the same trade-off met at commissioning — more glycol is not better.

Noise

Gurgling is air. Whistling is usually excessive flow or a restriction. Knocking suggests pipework expanding against a clip or through a wall without a sleeve — a solar primary moves a long way between ambient and stagnation, so clipping that is fine on a heating circuit can be noisy here.

Overheating and PRV discharge

Look at the controller's maximum store temperature setting, at whether the system is oversized for the actual demand, at a failed expansion vessel, and at low draw-off — a holiday period with a full store on a hot day is a perfectly normal cause of stagnation.

After rectification, and when to escalate

After any rectification

  1. Re-check system pressure against the recorded cold fill figure.
  2. Vent thoroughly, then run and vent again once hot.
  3. Verify the flow rate against the commissioned figure.
  4. Confirm the controller settings are as recorded.
  5. Verify the glycol with a refractometer if any fluid was lost or added.
  6. Leak check under pressure after a heat cycle, not before.
  7. Observe a full cycle: pump starting and stopping at the differentials, correct flow direction, sensible temperature rise across the collector.

Two procedures worth knowing in order

Replacing an expansion vessel. Cover the collectors and let the circuit cool → isolate the electrical supply to the controller and pump → drain down → collect the heat transfer fluid and check its pH and glycol concentration → replace the vessel → refill, reusing the fluid only if the tests passed. Checking the fluid before refilling is a step that is easily dropped, and it decides whether you are putting good fluid back or recycling exhausted fluid into a repaired system.

Draining a solar circuit. Cover the collectors first and let the fluid cool — draining a hot collector is how people are scalded. Then isolate the circuit breaker and spur supplying the solar controls, connect a hose to the drain point at the low end of the return, run it to a container set below the lowest part of the system, open the vent at the top of the circuit to let air in so the circuit drains, and drain into a secure container for disposal through the proper waste route.

When to escalate

Refer on rather than improvising where the fault involves structural concerns with the mounting or the roof, electrical work beyond your competence, unvented cylinder components when you are not trained and registered for unvented work, or a suspected manufacturing defect under warranty — where an unauthorised repair can void the cover.

And the fault that is not a fault

Low winter output is normal. So is a store that reaches 60 °C by mid-afternoon in July and then stops charging. So is a very hot collector while the family are away and nobody has drawn any hot water for four days.

Before diagnosing anything, establish what the customer expected and what the system was designed to deliver. Many solar callouts are answered by the performance estimate rather than by a spanner — and the engineer who can explain that clearly, without making the customer feel foolish for calling, is the one they call again.

The series

That completes the seven-module walk through the solar thermal course — principles and collectors, system types and layouts, regulations, survey and sizing, installation, commissioning, and fault finding. The course itself has 44 lessons with quizzes, flashcards, AI-marked short answers and forty-four interactive tasks, including a diagnostic simulator built from the scenarios in this article.

📝 10-Question Mock Test

Click an option to see whether you got it right. Explanations appear instantly — no submitting at the end.

Your score: 0 / 10
Question 1 of 10
How often should the heat transfer fluid be tested, and for what?
Question 2 of 10
The fluid tests at pH 6.2. What should be done?
Question 3 of 10
What is stagnation, and is it a fault?
Question 4 of 10
The pump is not running, every electrical check is sound, and the cylinder is at 65 °C. What is happening?
Question 5 of 10
A pump starts, runs briefly, stops and repeats, several times each morning. What is this and what causes it?
Question 6 of 10
A system has never performed since installation. Every component tests good. What should be checked first?
Question 7 of 10
A system has lost pressure over three months. Readings were all taken cold, there are no wet patches and the relief valve is dry. Where should you look?
Question 8 of 10
A sealed system loses a little pressure after each hot spell, with nothing wet indoors. What should you check?
Question 9 of 10
Circulation is sluggish although the pump is sound. What is the most likely cause?
Question 10 of 10
What is the correct order for replacing a solar expansion vessel?

The method is the point. Symptom, plausible causes, cheapest checks first — and the commissioning record as the thing that turns a reading into information, because a pressure or a flow rate means nothing on its own and a great deal against the value the system was left at.

And keep the third category in mind. Broken, set wrong, or working as designed — the last is more common than most engineers expect, and recognising it quickly is worth as much as any diagnostic skill.