An open-flued gas fire takes combustion air from the room and pushes its products of combustion up the chimney. If that flue doesn't draw — or the fire spills products back into the room — the danger is carbon monoxide. Two tests prove it's safe: the flue flow test and the spillage test. This guide covers both as you'd apply them to a fire. It's study material; only a Gas Safe registered engineer may carry out the work.

Standard. The test methods are in BS 5440-1, with appliance specifics in BS 5871 and the manufacturer's instructions, which take precedence.

Inspect before you test

First look the system over: correct flue type and size, sound joints, a liner where the chimney needs one, no blockage, and a suitable terminal. A catchment space should be present where required to catch debris. Tests confirm what a good inspection suggests — they don't replace it.

The flue flow test

Five steps on a line: inspect the flue, the terminal and the appliance before any test; flue flow test with a smoke pellet at the fire position, closure plate in place, watching the terminal and other rooms; spillage test with the fire lit, within 5 minutes of lighting unless the maker says otherwise, smoke match at the canopy, and if it spills run 10 more minutes and re-test; at worst case, room doors and windows shut and fans on, then internal doors open with fans elsewhere running; record the result and what you did. Still spilling: off, disconnect, never left in use.
Flow proves the flue works. Spillage proves it works with the room as it really is.

The flue flow test proves the empty flue draws and is clear along its whole length, before you rely on the fire. With the appliance off (or before it's connected), warm the flue if needed to establish a draught, then introduce smoke from a smoke pellet at the appliance position. The smoke should be drawn up and discharge cleanly at the terminal, with none escaping back into the room. If it doesn't clear, the flue is blocked or not drawing and must be put right before going further.

The spillage test

The spillage test proves the running fire clears its products. The method to BS 5440-1:

  1. Follow the manufacturer's method. Where it gives none, test within 5 minutes of lighting the fire (BS 5440-1:2023, 10.3.2.3).
  2. Hold a lit smoke match at the edge of the draught diverter / spillage point and watch that the smoke is drawn in (up the flue), not pushed out into the room.
  3. Test under worst-case conditions — the room's windows, doors and adjustable vents shut and any fan in the room running — because these can pull the flue into reverse. Repeat with any passive stack vent closed, and if there are fans elsewhere in the house, test again with every internal door open and every fan on maximum.
  4. If spillage is detected, run on a further 10 minutes and re-check (the flue may just need to warm through). If it still spills, switch off and don't leave the fire in use.
Why both, and why worst-case. Flue flow proves the flue is clear; spillage proves the fire clears its products in the real room. A fire can pass flow yet spill once an extractor fights it — exactly the dangerous, CO-producing condition you're testing for. Persistent spillage is an unsafe situation handled under the GIUSP.

Reading a spillage result

If the fire only spills with windows shut but is fine with them open, the room has insufficient ventilation — adding the correct air supply may resolve it. But if it spills regardless, the cause is usually poor flue performance, which no amount of ventilation will fix; the flue itself must be put right. Always interpret the result against the manufacturer's guidance.

  1. Inspect first: flue type/size, joints, liner, terminal, catchment space.
  2. Flue flow test: empty flue draws and is clear (smoke pellet) before relying on the fire.
  3. Spillage test: within 5 min of lighting, smoke match at the draught diverter, smoke drawn in not out.
  4. Worst case: doors/windows shut and extract fans on; with fans elsewhere, again with internal doors open and every fan on maximum.
  5. If it spills: run on 10 min and re-check; still spilling → switch off, don't leave in use.
  6. Spills only when closed up → ventilation; spills regardless → flue fault.
  7. Persistent spillage = unsafe situation under the GIUSP.

10-Question Mock Test

Click an option to see whether you got it right. Explanations appear instantly — no submitting at the end.

Your score: 0 / 10
Question 1 of 10
What is the danger if an open-flued fire spills its products into the room?
Question 2 of 10
The flue flow test proves:
Question 3 of 10
What is used to make smoke for the flue flow test?
Question 4 of 10
Where the maker gives no method, when is the spillage test done?
Question 5 of 10
During the spillage test the smoke match is held:
Question 6 of 10
Why repeat the spillage test with windows/doors shut and extract fans on?
Question 7 of 10
Spillage is detected; after a further 10 minutes it still spills. You should:
Question 8 of 10
A fire spills only when windows are shut, but is fine with them open. This points to:
Question 9 of 10
A fire that spills regardless of windows being open or shut usually has:
Question 10 of 10
In what order should you work?

Flow then spillage, always worst-case. Make the sequence automatic.

PlumbMate drills the HTR1 flue tests with quizzes and spaced repetition mapped to the gas ACS tickets.

🔥 Open the gas course →

Full ACS revision — CCN1, CPA1, CKR1, HTR1 & CENWAT · £29.99 for 60 days, or every course for a year at £59.99

Prefer to browse first? Back to the Gas Blog →