"Boiler interlock" is one of those phrases that sounds like a single component but isn't — it's a result achieved by wiring the controls together correctly. Get it right and the boiler only fires when there's real demand; get it wrong and the boiler short-cycles, wasting gas. This guide explains the idea and the parts. It's study material; only a Gas Safe registered engineer may carry out the work.

Standard & currency. Controls and interlock support efficient operation under BS 6798 and, in England, Boiler Plus (2018). Manufacturer's instructions and the wiring diagram take precedence.

What boiler interlock means

Boiler interlock means the boiler and its pump are switched off when there is no demand for heating or hot water — when every thermostat is satisfied, the boiler stops firing rather than cycling on and off against a system that doesn't need heat. It's delivered by the controls acting together so that "no demand anywhere" reaches the boiler as "stop."

Why TRVs alone don't count

A thermostatic radiator valve (TRV) throttles flow to its own radiator, but it doesn't tell the boiler to switch off. If TRVs were the only control, every TRV could close and the boiler would keep firing into a system that can't accept heat. So TRVs do not provide interlock — you need a room thermostat (in the reference room, which usually has no TRV) plus cylinder control to actually stop the boiler.

The controls that deliver interlock

S-plan and Y-plan

Two classic layouts wire these together:

Both give full interlock when correctly wired, because the boiler only runs while a valve is calling.

Automatic bypass and compensation

An automatic bypass valve lets a minimum flow circulate when most valves/TRVs have closed, protecting the pump and boiler from running against a closed system. For efficiency, weather or load compensation adjusts the boiler's flow temperature to conditions, keeping it modulating and condensing — these are among the measures that satisfy Boiler Plus.

Interlock is checked at commissioning. Confirm that with all thermostats satisfied (and the programmer calling), the boiler and pump actually stop. A system that keeps firing with no demand has no interlock — it's inefficient and not to current standards; correct the wiring/controls.
  1. Interlock = boiler/pump switch off when there's no heat or hot-water demand.
  2. TRVs alone don't provide interlock — they only throttle their own radiator.
  3. Delivered by: programmer + room thermostat + cylinder thermostat + motorised valve(s).
  4. S-plan = two 2-port valves; Y-plan = one 3-port mid-position valve.
  5. Automatic bypass protects pump/boiler when valves close.
  6. Weather/load compensation improves efficiency and helps meet Boiler Plus.
  7. Prove interlock at commissioning: no demand → boiler and pump stop.

10-Question Mock Test

Click an option to see whether you got it right. Explanations appear instantly — no submitting at the end.

Your score: 0 / 10
Question 1 of 10
Boiler interlock means:
Question 2 of 10
Do TRVs on their own provide boiler interlock?
Question 3 of 10
The room thermostat is usually located in a reference room that:
Question 4 of 10
The programmer decides:
Question 5 of 10
A motorised (zone) valve contributes to interlock by:
Question 6 of 10
An S-plan system uses:
Question 7 of 10
A Y-plan system uses:
Question 8 of 10
An automatic bypass valve is there to:
Question 9 of 10
Weather/load compensation improves efficiency by:
Question 10 of 10
How do you confirm interlock at commissioning?

Interlock is wiring, not a widget. Make the logic stick.

PlumbMate drills heating controls with quizzes and spaced repetition mapped to the gas ACS tickets.

🔒 PlumbMate Gas — coming soon

Full ACS revision — CCN1, CPA1, CKR1, HTR1 & CENWAT · £29.99/year · Launching soon

Prefer to browse first? Back to the Gas Blog →